Sprinkler Hydraulics by Harold S. Wass Jr. & Russell P. Fleming P.E

Sprinkler Hydraulics by Harold S. Wass Jr. & Russell P. Fleming P.E

Author:Harold S. Wass Jr. & Russell P. Fleming P.E.
Language: eng
Format: epub
ISBN: 9783030025953
Publisher: Springer International Publishing


Design Criteria: 0.25 gpm/sq. ft. over 2000 sq. ft.

Sprinkler Spacing in Horizontal Plane: 10 ft.

Branch-Line Spacing: 10 ft.

Minimum Sprinkler Flow: 10 ft. × 10 ft.= 100 sq. ft. × 0.25 gpm/sq. ft. = 25 gpm

Elevation Change Between Sprinklers:

Distance Between Sprinklers:

Number of Flowing Sprinklers:

Elongation of Operating Area along Branch Line: .

Since there are only 3 sprinklers on each branch line, extend the design area to additional branch lines supplied by the same cross main.