Analog Output Module: Converts the digital data value from the processor and converts this binary number into a proportional output signal. Serves as a D/A converter for the specific type of output range selected and configured for the module.

Example: 1746-NI4 Module

Voltage / Current RangeInteger Representation

-10 vdc to +10 vdc-32,768 to +32,767

0 to 10 vdc 0 to 32,767

0 to 5 vdc 0 to 16,384

1 to 5 vdc 3,277 to 16,384

-20 to +20 ma-16,384 to +16,384

0 to 20 ma 0 to 16,384

4 to 20 ma 3,277 to 16,384